How to Control a Single-Phase Motor from Multiple Locations?

Controlling the ON-OFF Operation of a 1-Phase Motor from Multiple Places using Contactor and Pushbuttons

In large industrial and commercial premises, there are scenarios where we need to control a three-phase or single-phase motor from different locations. Similarly, we may need to control a water pump motor from different places in domestic and home applications.  In the following wiring tutorial, we will discuss how to control the starting and stopping operations of a single-phase motor from different locations using a contactor and push-button switches, with the help of power and control circuit diagrams.

Related Posts:

Components Needed

  1. Single-Phase Motor
  2. Contactor
  3. Thermal overload Relay)
  4. 1-P & 2P-MCB
  5. 3 Nos. of NO/NC Pushbuttons
  6. Single Phase Supply
  7. Wires & Cables

Control Wiring Diagram

Controlling a Single-Phase Motor from Multiple Locations

Wiring the Control Circuit

Power Circuit:

  1. Wire and connect the L1 and L3 terminals of the contactor to the 2-pole MCB via Phase and Line wires.
  2. Connect a 2-pole MCB to the single-phase 120V to 230V power supply, mainly from the 120V-240V panel, 230V consumer unit or distribution board.
  3. Wire and connect the L1 and L3 terminals of the contactor to the output of the 2-pole MCB via Phase and Line wires. Keep in mind that the O/L relay is already connected to the contactor.
  4. Connect the T1 and T3 terminals of the overload relay to the “L” and “N” terminals of the single-phase motor.
  5. Connect the earth/ground wire to the motor terminal for proper protection.

Related Posts:

Control Circuit:

  1. Connect a wire to the first terminal of each start pushbutton (local and remote). Now, connect this wire to the 13-NO terminal of the contactor. Add a jumper wire between the 13-NO and A1 terminals of the contactor.
  2. Connect a wire to the second terminal of each start pushbutton (local and remote). Now, connect this wire to the 95-NC terminal of the thermal overload relay.
  3. Connect all three local and remote stop pushbuttons in series to the 95-NC terminal of the thermal O/L. Then, connect a wire from the last stop pushbutton to the 14-NO terminal of the contactor.

Working of the Circuit